Issue
An External Fan boundary condition is applied just upstream of a diffuser section. After running the analysis, the resultant operating point was not on the specified fan curve, and indicated a negative flow rate.
Solution
The Solver was unable to determine a realistic operating point because the external fan boundary condition is too close to the diffuser section. The solution is to extend the geometry upstream to separate the External Fan boundary condition from the diffuser section.
AUTODESK DOES NOT GUARANTEE THAT YOU WILL BE ABLE TO SUCCESSFULLY DOWNLOAD OR IMPLEMENT ANY SERVICE PACK OR WORKAROUND, OR ANY OF THE TIPS, TRICKS, EXAMPLES OR SUGGESTIONS OUTLINED IN ANY AUTODESK PRODUCT SUPPORT TECHNICAL DOCUMENTS. TECHNICAL DOCUMENTS, SERVICE PACKS AND WORKAROUNDS ARE SUBJECT TO CHANGE WITHOUT NOTICE TO YOU. AUTODESK PROVIDES TECHNICAL DOCUMENTS, SERVICE PACKS AND WORKAROUNDS "AS IS" WITHOUT WARRANTY OF ANY KIND, WHETHER EXPRESS OR IMPLIED, INCLUDING WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE. IN NO EVENT SHALL AUTODESK OR ITS SUPPLIERS BE LIABLE FOR ANY DAMAGES WHATSOEVER INCLUDING DIRECT, INDIRECT, INCIDENTAL, CONSEQUENTIAL, LOSS OF DATA, OR LOSS OF BUSINESS PROFITS OR SPECIAL DAMAGES, THAT MAY OCCUR AS A RESULT OF IMPLEMENTING ANY SERVICE PACK OR WORKAROUND, OR ANY SUGGESTION OUTLINED IN ANY AUTODESK PRODUCT SUPPORT TECHNICAL DOCUMENT, EVEN IF AUTODESK OR ITS SUPPLIERS HAVE BEEN ADVISED OF THE POSSIBILITY OF SUCH DAMAGES.